Standards

HVAC, Standards

ASHRAE 62.1

// MEPVAULT ASHRAE 62.1 — VRP MIN OUTDOOR-AIR CALCULATION TABLE 6.2.2.1 + VENTILATION RATE PROCEDURE USE Rp L/s·person Ra L/s·m² DENSITY (/100m²) V_BZ FOR 100m² (L/s) Office (occupied) 5 0.06 20 5×20 + 0.06×100 = 106 Conference room