Plumbing Pipe Sizing IS 1172 — Cold and Hot Water Systems India

Plumbing Pipe Sizing IS 1172 — Cold and Hot Water Systems

IS 1172 (Code of Basic Requirements for Water Supply, Drainage and Sanitation) is the foundational Indian standard for plumbing design. For MEP engineers, it provides the loading unit values and demand flow rates needed to size water supply pipes in Indian buildings. This article walks through the complete pipe sizing process with a worked example.

1. IS 1172 Loading Units — Water Consumption per Fixture

Plumbing Fixture

Loading Units (Cold)

Loading Units (Hot)

Flow Rate (L/min)

WC (cistern flush)

3

9 L/flush

WC (flush valve)

6

9 L/flush

Washbasin (tap)

1

1

8–10 L/min

Shower (mixer)

2

2

8–12 L/min

Bath tub

3

3

15–20 L/min

Kitchen sink (domestic)

2

2

10–12 L/min

Dishwasher (commercial)

4

15–20 L/min

Washing machine (domestic)

3

2

12–15 L/min

Urinal (cistern)

2

4.5 L/flush

Hose bib / garden tap

4

15–20 L/min

2. Simultaneous Demand Factor

Not all fixtures operate simultaneously. The simultaneous demand factor (diversity) reduces the design flow rate from the theoretical sum of all fixtures:

Total Loading Units

Probable Flow Rate (L/min)

Notes

5

12

Low-rise residential

10

16

Small floor / flat

20

25

Typical residential floor

50

42

Small hotel floor

100

60

Medium hotel or office floor

200

90

Large floor plate

500

150

Full building main supply

1000

220

Large complex

Note: Simultaneous demand is derived from IS 1172 probability curves. Actual flow rates depend on usage pattern — hospitals and hotels may have higher coincidence factors than offices.

3. Pipe Sizing from Flow Rate

Once the probable simultaneous flow rate is determined, pipe size is selected to maintain velocity within acceptable limits:

Application

Max Velocity (m/s)

Min Velocity (m/s)

Notes

Cold water main

2.0–2.5

0.6

Higher velocity causes noise in CPVC

Hot water supply

1.5–2.0

0.5

Lower velocity — thermal expansion

Cold water risers

1.5–2.0

0.5

Reduce noise in riser shafts

Branch to fixture

1.0–1.5

0.3

Final connections

Hose station / fire point

2.5–3.0

Separate fire water pipe

Pipe Flow Capacity Reference

Pipe Size (OD)

CPVC Flow @ 2 m/s (L/min)

GI / MS Flow @ 2 m/s (L/min)

Typical Application

20 mm

25

22

Single flat — bathroom branch

25 mm

40

35

Small flat cold water main

32 mm

65

58

2–3 flat riser or hotel room branch

40 mm

100

90

Small floor riser

50 mm

155

140

Medium riser, 8–10 flats per floor

63 mm

250

225

Large riser, 15–20 flats per floor

75 mm

355

320

Building main, 25–30 flats

90 mm

510

460

Large building main

110 mm

760

680

Campus or large hotel main supply

4. Worked Example — 100-Room Hotel, Each Floor 20 Rooms

Parameter

Value

Number of guestrooms per floor

20

Fixtures per room

WC × 1, washbasin × 1, shower × 1, bath × 1

Loading units per room (cold)

3+1+2+3 = 9 LU

Loading units per floor (cold)

20 × 9 = 180 LU

Probable flow per floor (from IS 1172 curve)

~84 L/min

Selected riser size (cold) @ 2 m/s

63 mm CPVC (250 L/min capacity)

Hot water loading units per room

1+2+3 = 6 LU

Hot water loading per floor

20 × 6 = 120 LU

Probable hot water flow per floor

~62 L/min

Selected hot water riser size @ 1.5 m/s

63 mm CPVC (188 L/min capacity at 1.5 m/s)

Building cold water main (5 floors)

5 × 84 = 420 L/min (with 0.85 diversity)

Building main pipe size

110 mm (760 L/min capacity — 55% utilisation)

5. Pipe Materials — Indian Market

Material

Standard

Max Temp (°C)

Pressure (bar)

Best For

Notes

CPVC

ASTM F441 / IS 15778

93°C

17 bar (cold)

Hot and cold water — most common 5-star

Chemical resistant, smooth bore, no scale

UPVC

IS 4985

60°C

16 bar

Cold water only

Not for hot — softens

GI (galvanised iron)

IS 1239

60°C

15 bar (medium)

Cold water mains, fire water

Scale buildup — reduced bore over time

PPR (polypropylene random)

DIN 8077

95°C

20 bar

Hot and cold — European standard

Growing in India — good hot water performance

Stainless steel (SS 304)

IS 6913

120°C

High

5-star hotels, hospitals, food industry

Premium — excellent lifespan, no corrosion

Copper

IS 7534

200°C

High

Hospitals, UK/European standard buildings

Limited in India — cost and availability