Electrical Cable Sizing IS 1554 — Worked Example
Cable sizing is one of the most fundamental electrical engineering calculations, yet it is frequently done incorrectly in Indian projects — resulting in undersized cables that overheat and create fire risk, or oversized cables that waste money. This article walks through the complete IS 1554 cable sizing methodology with a full worked example.
1. IS 1554 — Overview
IS 1554 (Specification for PVC insulated cables for working voltages up to and including 1100 V) is the primary Indian standard for LV power cables. IS 1554 Part 1 covers single-core cables; Part 2 covers multicore cables. For cable sizing, the relevant parameters from IS 1554 are the current-carrying capacity tables and the derating factor methodology.
2. Cable Sizing Steps
Step | Parameter | Method |
1 | Design current (Ib) | Calculate load current from power, voltage, power factor |
2 | Protection device rating (In) | In ≥ Ib — select standard fuse or MCB/MCCB size |
3 | Current rating required (It) | It ≥ In — after applying derating factors |
4 | Select cable (Iz) | Iz ≥ It — select from IS 1554 tables |
5 | Voltage drop check | Calculate voltage drop — must be ≤ 2.5% for power circuits |
6 | Short circuit check | Verify cable withstands fault current until protection clears |
3. Derating Factors
The current ratings in IS 1554 are based on standard conditions: 30°C ambient air, single circuit, installed in free air. Real installations deviate from these conditions — derating factors must be applied.
Ambient Temperature Derating (Ca)
Ambient Temperature (°C) | Derating Factor Ca (PVC insulation) |
25 | 1.06 |
30 (reference) | 1.00 |
35 | 0.94 |
40 | 0.87 |
45 | 0.79 |
50 | 0.71 |
Note: In Indian electrical rooms and cable trenches, ambient can reach 45–50°C in summer — always check actual conditions and apply appropriate Ca.
Grouping Derating (Cg)
Number of Cables / Circuits | Derating Factor Cg (touching) |
1 (reference) | 1.00 |
2 | 0.80 |
3 | 0.70 |
4 | 0.65 |
5 | 0.60 |
6 | 0.57 |
7–9 | 0.52 |
10–12 | 0.50 |
Installation Method Derating
Installation Method | Typical Derating vs Free Air |
Free air (clipped or on ladder) | 1.00 (reference) |
On cable tray, single layer | 0.95 |
In conduit (in wall, PVC) | 0.77 |
Buried direct in ground | Depends on soil thermal resistivity — see IS 1554 |
In cable duct (underground) | 0.75 |
4. Worked Example
Cable from MDB to an air-handling unit (AHU) with the following parameters:
Input Parameter | Value |
AHU motor power | 15 kW |
Supply voltage | 415V 3-phase 4-wire |
Power factor | 0.85 |
Efficiency | 92% |
Ambient temperature in cable route | 40°C |
Installation method | Cable tray — 3 circuits touching |
Cable length | 35 m |
Cable type | IS 1554 PVC armoured multicore |
Step 1 — Design Current
Ib = P / (√3 × V × PF × η) = 15,000 / (1.732 × 415 × 0.85 × 0.92) = 26.7 A
Step 2 — Protection Device
Select 32A MCB (In = 32A ≥ Ib = 26.7A) ✓
Step 3 — Required Current Rating After Derating
Combined derating factor = Ca × Cg = 0.87 (40°C) × 0.70 (3 circuits) = 0.609
Required It = In / combined derating = 32 / 0.609 = 52.5 A
Step 4 — Cable Selection
From IS 1554 tables: 10 mm² 4-core PVC armoured cable has Iz = 57 A in free air. After derating: 57 × 0.609 = 34.7 A — insufficient.
Try 16 mm² 4-core: Iz = 76 A in free air. After derating: 76 × 0.609 = 46.3 A — still insufficient.
Try 25 mm² 4-core: Iz = 99 A in free air. After derating: 99 × 0.609 = 60.3 A ≥ 52.5 A ✓
Preliminary cable selection: 25 mm² 4-core IS 1554 PVC armoured cable.
Step 5 — Voltage Drop Check
Voltage drop formula (3-phase): ΔV = √3 × I × L × (R cosφ + X sinφ) / 1000
For 25 mm² cable: R = 0.927 mΩ/m, X ≈ 0.08 mΩ/m
ΔV = 1.732 × 26.7 × 35 × (0.927 × 0.85 + 0.08 × 0.527) / 1000 = 1.25 V
% Voltage drop = 1.25 / 415 × 100 = 0.30% — well within 2.5% limit ✓
Result
Select: 25 mm² 4-core PVC armoured cable to IS 1554, with 32A MCB protection. Cable is satisfactory for current rating and voltage drop.
5. Summary Checklist
- Calculate design current (Ib) accurately — include power factor and efficiency
- Select protection device In ≥ Ib
- Determine all applicable derating factors — ambient temp + grouping + installation method
- Required It = In ÷ combined derating factor
- Select cable with Iz ≥ It from IS 1554 current rating tables
- Verify voltage drop ≤ 2.5% for power, ≤ 1% for lighting
- Check fault current withstand — especially for long cables or large fault currents
Related Reading on MEPVAULT
Continue your research on related topics from our engineering library:
