Condenser Water Sizer & Pump Head Calculator
MEPVAULT CW Sizer
OPEN LOOP CONDENSER WATER:
Direct GPM input. Steel/GI C-Factors are conservatively derated (C=120) to account for open loop scaling & fouling per ASHRAE/Carrier standards.
Direct GPM input. Steel/GI C-Factors are conservatively derated (C=120) to account for open loop scaling & fouling per ASHRAE/Carrier standards.
System Flow
GPM
Material & Constraints
FPS
ft/100'
Pipe Routing (Friction Head)
ft
Valves & Specialties (Friction Head)
Equipment & Static Head
ft hd
ft hd
Sizing Options
⚠️ VEL < 3 FPS (Fouling Risk)
| Option | Size | Vel (FPS) | Fr (ft/100') |
|---|
Total Equiv Length
-- ft
Pipe Friction Head
-- ft hd
Total Required Pump Head
-- ft hd
Equip & Static Head Included: -- ft
Add to Schedule
MEPVAULT CW Sizing & Pump Head Schedule
Project: Unnamed | Units: Imperial | Open Loop Hazen-Williams
| Tag / Ref | Mat. | Flow (GPM) |
Size (in) | Vel (FPS) |
Fric (ft/100') |
L_Eq (ft) |
Fittings | Eq + Stat Head (ft) |
Pump Head (ft hd) |
Act |
|---|
* Fitting Equivalent Lengths (L/D ratios) derived from Carrier System Design Manual (Part 3) & ASHRAE Fundamentals.
* Total Pump Head = Pipe Friction + Fittings + Chiller PD + Cooling Tower Lift.
* Total Pump Head = Pipe Friction + Fittings + Chiller PD + Cooling Tower Lift.